|
WHAT
IS WRONG WITH YOUR AIR CONDITIONER?
|
|
It
doesn't turn on at
all
The
fan runs but there's no cold
air
The
air is cool but doesn't seem cold
enough
The
unit never turns
off
There
is water sloshing around
inside
The
unit try's to start for a few seconds and
then
quits
A
motor is running but there is no air
blowing
The
unit rattles loudly when it turns
off
Water
leaks out the front of the
unit
The
air smells
musty
|
|
It
doesn't turn on at all
|
|
Check to
see if there is power getting to the air
conditioner. If it is a 110-volt unit,
plug a lamp or other device into the same
outlet the air conditioner is plugged
into. If there's no power, check the fuses
or circuit breakers. If there's still no
power, you will need to contact a
qualified electrician to restore power to
the outlet.
If there is power to the appliance but it
is still completely dead there may be a
problem in one or more of the following
areas:
- Wiring
(Inspect for any broken or burnt
wiring)
- Thermostat
- Compressor
- Overload
and/or relay
- Selector
switch
- Control
board
Work on
these areas of an appliance may require
help from an appliance repair person or
other qualified technician.
|
|
|
|
The
fan runs but there's no cold
air?
|
|
Is the air
conditioner completely dead? See section
1. Is the thermostat knob turned to the
proper setting? Is the compressor motor
running? The compressor is a
football-sized case with no apparent
moving parts. It is located inside the air
conditioner at the center. Is it humming
or making any kind of continuous noise or
causing the lights to dim? If it is making
a continuous noise, and your air
conditioner is still not cooling at all,
there may be a serious problem with one or
more of these areas:
- Compressor
- Condenser
- Evaporator
These
items are not user serviceable. You will
need to contact a qualified appliance
repair technician to repair these
components.
If the compressor is not running but you
do have power to the air conditioner there
may be a problem in one or more of these
areas:
- Compressor
- Overload
and/or relay
- Thermostat
(Open thermostat)
- Burnt
wiring
- Bad
selector switch
- Capacitor
|
|
|
|
The
air is cool but doesn't seem cold
enough
|
|
If the air
doesn't seem cool enough it is necessary
to use a thermometer to check the
difference in temperature between the air
going into the unit and the air being
blown into the room. Ideally, the
temperature difference should be more than
15 degrees. For example, if the
temperature going into the air conditioner
is 80 degrees, the temperature coming out
of the unit should be at least 65 degrees
or less. If the difference is 15 degrees
or more there is probably no cause for
concern. If the temperature difference is
less than 15 degrees you should check the
following:
Check to
make sure the air damper is closed. If
it's open, it will bring in outside air
and reduce the efficiency of the unit.
During the
winter season many people cover their air
conditioners to protect the unit from the
weather. In the spring or summer they will
sometimes forget to remove the cover. If
your unit has a cover on the outside
portion of the air conditioner remove the
cover first.
The
condensing coils will always be on the
"warm" side of the air conditioner. That
is, on the side that faces outside of the
room to be cooled. Air is drawn into the
back of the air conditioner on the sides
through vent slots and is blown directly
out through the condenser coils. If the
coils get clogged with lint, dust and dirt
the cooling system cannot provide the
cooling necessary. To clean the coils it
will be necessary to remove the entire
cover of the air conditioner or pull it
out of the wall to gain access to the
coils. They can be cleaned by blowing
compressed air at them or by using a soft
bristle brush to wipe the dirt off. It is
important to also clean any dirt or lint
build-up in the bottom of the air
conditioner so the condensate water will
be picked up by the condensing fan slinger
properly.
|
|
|
|
|
|
This is
normal on some models when fan is set to
run constantly.
If the unit is supposed to turn off and it
doesn't, it will be necessary to check
several things.
- First,
is the unit cooling properly? See the
section entitled "The air is cool but
doesn't seem cold enough."
- Next,
is the temperature of the room
adequately cool? If the room
temperature is cold enough try setting
the thermostat to a higher temperature.
If the unit then seems to work properly
leave the thermostat set to the higher
temperature.
- If the
unit is cooling properly when it is
turned on and the room is not cool
enough the problem is probably that the
unit is trying to cool an area that is
too large for its capacity. Use the
following chart to find the appropriate
size air conditioner to
use:
AREA TO BE
COOLED / CAPACITY (BTU/HR)
100 to 150 square feet = 5,000
150 to 250 square feet = 6,000
250 to 300 square feet = 7,000
300 to 350 square feet = 8,000
350 to 400 square feet = 9,000
400 to 450 square feet = 10,000
450 to 550 square feet = 12,000
550 to 700 square feet = 14,000
700 to 1000 square feet = 18,000
If the
room is heavily shaded, reduce needed
capacity by 10%
If the room receives a lot of direct sun,
increase needed capacity by 10%
Add 600 Btu/Hr for each person in the room
if there are more than two people
If the unit is for a kitchen, increase the
capacity by 4,000-6,000 Btu/Hr.
If the room size is too big for the air
conditioner you have two possible choices.
Either decrease the room size by shutting
some doors or partitioning off an area of
the room. Or, increase the BTU of the air
conditioner for that room by installing a
different air conditioner with a higher
BTU rating.
|
|
|
|
There
is water sloshing around inside
|
|
All window
air conditioners will remove moisture from
the air if there is any. Most window air
conditioners collect this moisture in the
bottom pan of the air conditioner and
attempt to evaporate the moisture. The
evaporation process works as follows:
First, the water drips down off of the
cold evaporator coils on the front of the
unit. Then the water collects in the
bottom of the air conditioner base, the
"pan." If the air conditioner is installed
properly it will be tilted slightly
back.
The water then collects near the back of
the unit. On some units, the fan blade
used to cool the rear condensing coils
will have a rim on the outside of the fins
of the blade. This rim, or "slinger," will
come close to touching the inside of the
air conditioner pan when the fan is
spinning. As the water collects in the pan
and reaches the depth necessary for the
fan ring to touch it, the ring will lift
some of the water up and the fan will blow
it at the condensing coils. Because the
coils are warm, they will evaporate the
moisture to the outside.
While this is happening it is normal to
hear water splashing and sloshing around.
As long as there is no water leaking
inside the room that is being cooled there
is no cause for concern.
Never drill into the bottom of and air
conditioning unit to "let the water
out."
|
|
|
|
The
unit tries to start for a few seconds and
then quits
|
|
Every air
conditioner has a motor called a
compressor. The compressor provides the
cooling capacity for the air conditioner.
If the compressor or its electrical
controls are defective the compressor may
try to start, fail, and create an
electrical overload. If the unit does
create an overload, every compressor
circuit is also equipped with an overload
safety switch. The safety switch is
designed to protect the compressor from
burning out. The safety switch will cut
the power to the compressor for a certain
length of time and then reset itself. When
it resets it will allow the electricity to
flow to the compressor once again. If the
compressor then starts, the unit should
function normally. If the compressor
doesn't start when the overload resets,
the overload will again cut the
electricity to the compressor. This cycle
will continue indefinitely. (Always allow
three to five minutes before restarting
the compressor.) If this situation is
occurring, unplug the air conditioner and
get help from a qualified repair
technician. This problem is often fatal to
the air conditioner because the cost of
repair often exceeds the price of a new
air conditioner.
|
|
|
|
A
motor is running but there is no air
blowing
|
|
Every air
conditioner is equipped with at least two
motors, the compressor and the fan motor.
It is possible for the fan motor to be
defective and the compressor to be
running. If this is the case the unit will
appear to be running and may even sound
"normal" but no air is blowing out the
front or back of the unit. If, after
removing the cover of the unit you
discover the fan blade is very stiff and
difficult to rotate, the fan motor should
be replaced. If the fan blade turns freely
the circuit powering the fan motor will
require electrical troubleshooting. It
will be necessary to have a qualified
technician locate the cause of the
problem, which may be either a problem
with the capacitor, the selector switch or
the motor itself.
|
|
|
|
The
unit rattles loudly when it turns
off
|
|
The
compressor in all window air conditioners
is a powerful motor. When it starts up -
and especially when it shuts off - the
whole air conditioner can shake, sometimes
loudly. Usually there is nothing that can
be done to correct this problem. However,
it is possible that the compressor
mounting pads and brackets are worn out or
missing. If that is the case the pads and
brackets can sometimes be ordered and
replaced.
Be sure that the air conditioner is
securely mounted in the window frame if
the unit shakes at all. It is possible for
the unit to shake free of the frame if not
installed properly.
|
|
|
|
Water
leaks out the front of the unit
|
|
It is
normal for water to collect in the lower
base of an air conditioner. See the
section entitled: "There is water sloshing
around inside." If water leaks out the
front it is usually because the unit is
tilted forward in the window frame. All
air conditioners should be installed so
they tilt slightly back to allow for
proper removal of the condensation
collected.
|
|
|
|
|
|
Air
conditioners remove moisture from the air.
The water collects in the base of the
unit. Under normal conditions this water
will be evaporated out of the unit.
However, it is possible for some water to
sit stagnant in the base of the air
conditioner for extended periods of time.
There is no easy way to prevent this
problem. The problem will be reduced if
you carefully clean the base of the inside
of the air conditioner at least once a
year. That will keep any dirt, lint or
dust from absorbing the water and allowing
mold and mildew to grow. Also, replace the
filter behind or in the front cover.
|